undefined
undefined
undefined
+
  • undefined
  • undefined
  • undefined

ZXDU48 B600 60A 2*RETIF ZXD1500 48V DC V5.0

Focused on providing fiber optic communication equipment and supporting products to global customers

Category:

  • Description
  • ZXDU48 B600 Overview

    ZXDU48 B600 is a 1U high/19 inch wide embedded communication DC power system can be insert 1*monitoring module ZTE CSU520Y 2*rectifier module ZTE ZXD1500. which is -48 V Series communication equipment power supply.
    Adopt single-phase three-wire AC input mode (L/N/PE), suitable for 220 V/380 V power grid. At the same time, compatible with 110V dual live wire access.
    Fully configured with 2 ZXD1500 (V5.0) rectifiers, rated output power is 3200 W, maximum output current is 60A/53.5 V DC.
    The ZXDU48 B600 DC power system can be installed into a 19-inch cabinet to supply power to -48V communication devices.


    Specification

    Item

    Description

    Operating temperature

    -33℃ to +55℃

     

    Sheds the load when they system operates in a temperature higher than 55℃

    Powers off automatically when the system temperature is higher than 75℃

    Storage temperature -45℃ to +70℃
    Relative humidity 5% to 95% (non-condensing). It is recommended that the relative humidity is in the range of 40% to 60%
    Altitude

    0m to 2000m: Outputs in full power

     

    2000m to 3000m: Derated by 1% for every 100m increase of altitude

    Space requirement

    The system must be installed in a 19-inch cabinet or rack.

     

    The system must be horizontally installed. The cabinet must be definitely vertical. No bump is allowed.

    There should be no liquid or conductive objects within, or dropping into the cabinet.

    The system must not be installed near any water, corrosive gas, or explosive materials.

    There should be no conductive dust or electromagnetic interference in the vicinity.

    System capacity 3200W/66A. Two ZXD1500 rectifiers are required for full configuration
    System efficiency Peak efficiency: 95%
    Power limitation based on the input voltage AC input ≤85 V± 5 V The output power of the rectifier is 0%.
    AC input (85 V±5 V) to 110 V The power drops linearly. The output power of the rectifier ranges from 40% to 60% of the overall power.
    AC input 110 V to 176 V The power drops linearly. The output power of the rectifier ranges from 60% to 100% of the overall power.
    AC input 176 V to (305 V±5 V) The output power of the rectifier is 100%.
    AC input >305 V±5 V The output power of the rectifier is 0%.
    Power limitation based on the temperature Ambient temperature: -33℃ to +55℃ The output power of the rectifier is 100%
    Ambient temperature: +55℃ to +75℃ The output power decreases linearly as the temperature rises. When the environmental temperature reaches 70°C, the output power is no lower than 62.6% of the maximum power.
    Ambient temperature: >+75°C The output power of the rectifier is 0% (power-off protection)
    Over all noise (sound pressure) ≤68 dB(A)
    Network architecture for monitoring RS232 ports connected in series
    Mean time between failures MTBF≥3.2x 10⁵ h
    Design life 10 years to 15 years
    Input AC features AC input mode Three-wire single-phase system (LN/PE). Compatible with dual-live wires (L1/L2/PE)
    Input AC voltage

    Rated phase-to-neutral voltage: 200 V to 240 V

     

    Range of phase-to-neutral voltage: 85 V to 295 V

    Input frequency

    Rated frequency: 50 Hz/60 Hz

     

    Frequency range: 45 Hz to 66Hz

    Input PF The PF is no lower than 0.996 at the rated load.
    Total harmonic distortion THD≤5% when the system operates at a power ranging from 30% to 100% of the rated power.
    AC lightning protection A lightning protection module is embedded in the rectifier.
    AC power distribution Number of AC inputs  1
    AC input circuit breaker 3xrimping terminals
    Stanby AC output
    Protection feature AC overvoltage protection The overvoltage protection takes effect when the single-phase input voltage is higher than the AC overvoltage protection threshold.
    AC undervoltage protection The undervoltage protection takes effect when the single-phase input voltage is lower than the AC under voltage protection threshold.
    Output DC properties Rated DC output voltage -53.5 V DC
    Range of the DC output voltage Continuously adjustable from -41 V to -58 V (adjust by the CSU)
    Voltage drop in the cabinet ≤500 mV
    Regulated voltage precision ≤0.6%
    Psophometrically weighted noise voltage ≤2 mV
    DC lightning Maximum current of the lightning arrester: Imax = 3 kA (8/20 μs)
    DC power distribution Battery inputs One input. 1 x 30 A, configured with a 40 A fusible link
    Protection feature Power-off protection mode Battery Low Voltage Disconnect (BLVD)
    DC load outputs Two outputs. 2 x 20 A, configured with a 40 A fusible link
    DC overvoltage protection The overvoltage protection takes effect when the output voltage is higher than the DC overvoltage protection threshold.
    DC undervoltage protection The undervoltage protection takes effect when the output voltage is lower than the DC overvoltage protection threshold.
    Battery undervoltage protection The power-off protection takes effect when the battery voltage is lower than the power -off voltage protection threshold.
    Dimensions

    1U height / 19-inch width

     

    43.6 mm x 482.6 mm x 260 mm (Height x Width x Depth)

    Overall weight (including the rectifiers) Around 8 kg
    Installation mode Embedded in a 19-inch cabinet